Wimmera Mallee Contracting Pty Ltd

Wimmera Mallee Contracting Pty Ltd Electrical Inspection Services Western Victoria

WMC Pty Ltd run by Quinn Mclean since 2020 G class LEI with 13 plus years, Covering Switch Boards, Temp Perm, CT Metered supply, Solar cogeneration, Stand a loan & Generator connections in the Wimmera Mallee Region

9 weeks
02/09/2026

9 weeks

Monday connection day 10-12 months work now to start commissioning everything
22/06/2026

Monday connection day 10-12 months work now to start commissioning everything

Hire cable Rolla turned up late last week
21/06/2026

Hire cable Rolla turned up late last week

Big Switchboard Monday Big Motors Kms cable tray
19/06/2026

Big Switchboard Monday
Big Motors
Kms cable tray

Early start cold and wet last leg home sunset
18/06/2026

Early start cold and wet last leg home sunset

Lot and lots of battery’s done in the last few months
10/05/2026

Lot and lots of battery’s done in the last few months

Big Solar big day at work huge private system
09/05/2026

Big Solar big day at work huge private system

08/05/2026

Interesting solution

07/05/2026
06/05/2026

⚡COMPLIANCE ALERT: generating sets⚡

Let's jump right in!

1. Fault current availability.

The gen-set, depending on its size, may or may not have adequate fault current to trip protective devices under short circuit conditions. As per clause 2.6.2 of AS/NZS 3010:2017, all outgoing circuits must be protected against short circuit - unless you meet the exception to the above clause.

The easiest way is to measure the resistance of the consumer mains all the way through the windings of the gen-set. In other words:
1. Ensure the gen-set is OFF
2. Close all isolating switches on the gen-set
3. Measure the resistance between phases, and from phases to neutral, at the main switchboard
4. Measure the resistance of the protective earthing conductor from the main switchboard to the gen-set frame.

The resistance values obtained can then be plugged into Ohm's Law to determine the prospective fault current available for both phase-to-phase and phase-to-neutral faults, as well as phase-to-earth faults.

The resultant current value should be no less than the instantaneous tripping current of the protective device at the origin of the consumer mains at the gen-set. For example:

1. Your highest loop resistance measurement (say using the protective earthing conductor) is 0.3ohms
2. As per ohm's law, the lowest available fault current is 230/0.3=~765A
3. Your gen-set overcurrent device is a B63 circuit breaker, which has an instantaneous tripping current of 63*4=252A
4. Therefore, the consumer mains are protected against short circuit.

You can also re-test this live using an EFLI tester, or an NST.

You _can_ also calculate the prospective fault current available if provided with the internal impedance of the gen-set (e.g. 10%) using the following formula:

PFC=(S*100)/(693*Z)

Where S is the VA of the generator and Z is the internal impedance of the gen-set as a percentage. 693 is for three-phase gen-sets.

But my recommendation? Measure the resistances dead, and retest live using an EFLI tester or NST.

2. Neutral switching.

IF the gen-set is the sole supply to the electrical installation, you SHALL NOT switch the neutral at the gen-set isolating device (2.6.3 exception 2). Otherwise, you MUST switch the neutral at the gen-set.

The first scenario almost always applies when gen-sets are used to supply construction sites prior to grid supply availability.

In alternative or supplementary supply situations, the following applies:
1. The gen-set isolator MUST switch the neutral
2. Where hard-wired, the changeover device and main switch should not switch the gen-set neutral
3. Where plug-in, the changeover device MUST switch the gen-set neutral.

Thankfully, AS/NZS 3010:2017 has clear and useful figures to explain the various connection scenarios.

And remember: in all cases, gen-sets and their supplies are prescribed work and require inspection.

Got any questions? Ring Text or Email .

Address

3 Stawell Road
Horsham, VIC
3400

Opening Hours

Monday 9am - 5pm
Tuesday 9am - 5pm
Wednesday 9am - 1pm
Thursday 8:30am - 4:30pm
Friday 8am - 12pm

Telephone

+61417556878

Website

Alerts

Be the first to know and let us send you an email when Wimmera Mallee Contracting Pty Ltd posts news and promotions. Your email address will not be used for any other purpose, and you can unsubscribe at any time.

Contact The Establishment

Send a message to Wimmera Mallee Contracting Pty Ltd:

Shortcuts

Share